Honeywell C7012E1153 uv flame detector, self-checking
Category: Flame Detector/Sensor
Specifications
Product Details
Voltage: 240Vac, 50/60Hz
Mounting: 3/4" NPT
Temperature rating: -20°F to +175°F
Lead wire length: 8 ft
Honeywell C7012E1153 uv flame detector
Solid state electronic flame detectors for use with Honeywell Flame Safeguard controls and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels.
Mount horizontally, vertically or at any angle in between.
Provide quick electrical hookup with threaded conduit fitting and color-coded leadwires
Reduced nuisance shutdowns by wiring two in parallel.
C7012E1278 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell.
C7012A, E meets NEMA 4 standards with viewing window rated to 20 psi.
C7012C, F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper, Self-Checking
Application: Gas, Oil or Coal fired burners
Lead Length: 96 in. (2438 mm)
Power Consumption: 7.0 W
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 14740.01
Used With: Flame Amplifiers: R7247C, R7847C
View more about Honeywell C7012E1153 uv flame detector, self-checking on main site