Flame failure response time: 2 to 4 sec Fuel: Gas, oil & coal
Honeywell R7249A1003 amplifier
Solid state plug-in units respond to flame detector signal and indicate presence of flame. * Use with BC7000; R4140; R4075C,D,E; R4138C,D Flame Safeguard controls and appropriate flame detector and FSP5075A1, FSP5075A3 Flame Amplifier Modules. Type: Flame Amplifier Humidity Rating (%RH): 5 to 90% RH Vibration: 0.5 G continuous Weight: 8 oz. (227 g) Approvals: Canadian Standards Association: Certified: File No. LR1620, Guide No. 140-A-2 Control Safety Devices: Acceptable (CSD-1) Factory Mutual: Approved: Report No. 24181.01 Industrial Risk Insurers: Acceptable Underwriters Laboratories, Inc: Listed: File No. MP268, Guide No. MCCZ2