Honeywell RA890G1260 protectorelay
Category: Protectorelay
Specifications
Product Details
Voltage: 120 Vac
Flame failure response time: 0.8 sec
Alarm relay switching: SPDT
Safety switch timing: 15 sec
Honeywell RA890G1260 protectorelay
Primary control provides solid state, electronic flame safeguard protection for industrial and commercial single or dual fuel burners applications using Ultraviolet flame detectors.
* Design for interrupted ignition with intermittent pilot on gas burners, and interrupted or intermittent ignition on oil burners.
* Use with a C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector for flame sensing.
* Recycles if flame signal lost while in Run. Failure to establish pilot results in a lockout.
* Safe-start check prevents start-up if flame-simulating failure occurs in flame detector circuit.
* Includes SPDT alarm contacts.
* Solid state circuitry, eliminates warm-up and increases resistance to vibration.
* Mounts and removes easily through use of captive mounting screws.
* Mounting base is made of strong thermoplastic
Application:
Either a line or low voltage controller can be used
Frequency: 50 Hz; 60 Hz
Temperature Range: 60 Hz models -20°F to +115°F, 50 Hz models
-20°F to +105°F (50 Hz Models -29°C to +41°C, 60 Hz Models -29°C to +46°C)
Approximate, Dimensions: 5 in. high x 5 in. wide x 4 3/4 in. deep
(including subbase) (127 mm high x 127 mm wide x 121 mm deep (including subbase)
Approvals, Underwriters Laboratories Inc.: UL Listed: 120V models
only; File No. MP268, Guide No. MCCZ
Approvals, CSA: CSA Certified: 120V models only; File No. LR9S329
Approvals, Factory Mutual: Approved: Report No. 22013
View more about Honeywell RA890G1260 protectorelay on main site