Honeywell S4560D1135 ignition control
Category: Boiler & Burner Controller & Programmer
Specifications
Product Details
Voltage: 220-240Vac, 50Hz
Power consumption: 10 VA max
Honeywell S4560D1135 ignition control
Application:
The S4560 provides automatic ignition and control for burners in accordance with EN 298.
Specifications:
Model
S4560: 220-240 Vac, 50 Hz.
Suffix A: For atmospheric burners. Nonvolatile lock out in accordance with EN 298.
Suffix B: As suffix A except a built-in flame indication relay for modulating applications.
Suffix C: For fan assisted applications. Nonvolatile lock out in accordance with EN 298.
Suffix D: As suffix C except a built-in flame indication relay for modulating applications.
Suffix E: As suffix A except lock--out after flame lost during normal operation.
Suffix P: As suffix A except volatile lock out, reset by interrupting heat demand.
Suffix Q: As suffix B except volatile lock out, reset by interrupting heat demand.
Suffix R: As suffix C except volatile lock out, reset by interrupting heat demand.
Suffix T: As suffix D except volatile lock out, reset by interrupting heat demand
Ambient temperature
0-60 degree Celcius
Relative humidity
90% max. at 40 degree Celcius (non condensing)
Supply voltage
Line voltage, 220 V (--15%) ... 240 V (+10%), 50 Hz ( 2 Hz)
Power consumption: 10 VA max.
Alarm output: 1 A max
Flame indication relay: 1 A max
External ignition transformer: 1 A max
All outputs together: 3 A max
Electrical connection
High tension spark: 2.8 x 0.5 mm spade terminal.
Flame rod and ground: 6.3 x 0.8 or 4.8 x 0.8 mm spade terminal (depending on O.S. number).
Multiple connector: Molex 3001 series
Timing (depending on O.S. number)
Waiting time (Tw)/Prepurge time (Tp): 0-24 s
Safety time (Ts): 0-250 s
Stabilization time (Tstab): 0-15 s
Flame sensing
Flame sensing is based on the rectification principle.
Minimum flame current: 0.7 ←A
Response time ”ON”: < 200 ms (at 2 ←A flame current)
Response time ”OFF”: < 1 s
Maximum cable length: 1 m
Not protected against electrical shock.
Ignition
Integral electronic spark generator
Spark voltage: 12 kV at 40 pF load
Repetition rate: 12 Hz
Maximum cable length: 1 m
Not protected against electrical shock
View more about Honeywell S4560D1135 ignition control on main site